Technical Information
Technical data QuadCore UltraTech Precision Light Panel, for including thermal, acoustic, and fire performance information.
Applications
QuadCore® UltraTech Precision Light Panels are suitable for all internal cleanroom wall applications across a variety of sectors including pharmaceutical and bio-technology laboratories, healthcare, medical research and advanced technology facilities.
Available Lengths
| Standard Lengths (mm) |
|---|
| 300 - 2900 |
Dimensions, Weight & Thermal Performance
| Core Thickness (mm) | U-Value (W/m2K) | R-Value (m2K/W) | Weight (kg/m2) |
|---|---|---|---|
| 60 | 0.69 | 2.12 | 12.5 |
These values are in accordance with BS EN 14509, using Finite Element Analysis, and take into account any thermal bridging through the longitudinal joint.
The U-Values have been calculated using an aged thermal conductivity value of 0.018 W/mK.
Certification & Testing
Reaction to Fire
Reaction to Fire QuadCore® UltraTech Precision Lite Panels are classified B-s2,d0, when tested on the internal face of the product, according to the European Reaction to Fire classification system (Euroclasses) BS EN 13501-1: 2018 under the certified name KS300-1200UT-PL when using the following internal liners:
CLEANsafe 15
CLEANsafe 25
CLEANsafe 55
CLEANsafe 120
Please contact Kingspan Tech-eXchange for further information on certification and testing.
Air Tightness
The joint of the QuadCore® UltraTech Precision Lite can achieve air tightness of less than 0.003m³ /hr/m² at 50Pa in accordance with BS EN 14509 (BE EN 12114).
For further information on air tightness please contact Kingspan Tech-eXchange.
Water Tightness
The joint of the QuadCore® UltraTech Precision Lite Panel can achieve water tightness to 1200Pa (Class A) in accordance with BS EN 14509 (BS EN 12865).
For further information on air tightness please contact Kingspan Tech-eXchange.
Acoustic
| Frequency (Hz) | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 |
|---|---|---|---|---|---|---|---|---|
| SRI (dB) | 20 | 15 | 17 | 23 | 18 | 25 | 40 | 46 |
Sound Reduction Index (SRI)
QuadCore® UltraTech precision Panels have a predicted single figure weighted sound reduction of Rw = 24dB. Results are based on panels of similar profile and core material.
Product Tolerances
| Length | Width | Thickness | Flatness (per m) | End Squareness |
|---|---|---|---|---|
| +/- 1.5mm | +/- 1.5mm | +/- 2mm | +/- 1mm | +/- 2mm |
Warranty
Kingspan Panel Warranty covering the following subject to project specific information:
Up to 25 years structural
Up to 25 years external coating
Please contact Kingspan Tech-eXchange for further information.
Downloads
Access product brochures, datasheets, and technical documentation to support specification and project planning.