Technical Information

Technical data QuadCore UltraTech Precision Panel, for including thermal, acoustic, and fire performance information.

Applications

QuadCore® UltraTech Precision Panels are suitable for all internal cleanroom applications across a variety of sectors including pharmaceutical and bio-technology laboratories, healthcare, medical research and advanced technology facilities. 60mm QuadCore® UltraTech Precision Panels have an optional 25mm UL rated service void along the length of the panels.

Available Lengths
Standard Lengths
Standard Lengths (mm
300 - 5700

* Variable widths available as non-standard in 10mm increments. Minimum width 150mm.

Dimensions, Weight & Thermal Performance
Dimensions, Weight & Thermal Performance
Core Thickness (mm)6080
U-Value (W/m²K)0.470.36
R-Value (m²K/W)2.122.77
Weight (kg/m²)16.517.3

These values are in accordance with BS EN 14509, using Finite Element Analysis, and take into account any thermal bridging through the longitudinal joint.

The U-Values have been calculated using an aged thermal conductivity value of 0.018W/mK.

Certification & Testing

Reaction to Fire

QuadCore UltraTech Precision Panels are classified B-s1,d0 for the 60mm option and B-s2,d0 for the 80mm option , when tested on the internal face of the product, according to the European Reaction to Fire classification system (Euroclasses) BS EN 13501-1:2018 under the certified name KS1200 UT-P QuadCore® CS15 when using the following internal liners: CLEANsafe 15, CLEANsafe 25, CLEANsafe 55, and CLEANsafe 120.

Please contact Kingspan Tech-eXchange for further information on certification and testing.

Air Tightness

The joint of the QuadCore® UltraTech Precision Panel can achieve air tightness of less than 0.003m3/hr/m2 at 50Pa in accordance with BS EN 14509 (BE EN 12114). For further information on air tightness please contact Kingspan Tech-eXchange.

Water Tightness

The joint of the QuadCore® UltraTech Precision Panel can achieve water tightness to 1200Pa (Class A) in accordance with BS EN 14509 (BS EN 12865). For further information on air tightness please contact Kingspan Tech-eXchange.

Acoustic
Sound Reduction Index (SRI)
Frequency (Hz)631252505001000200040008000
SRI (dB)2015172318254046

QuadCore® UltraTech Precision Panels have a predicted single figure weighted sound reduction of Rw = 24dB. Results are based on panels of similar profile and core material.

Product Tolerances
Product Tolerances
LengthWidthThicknessFlatness (per m)End Squareness
+/- 1.5mm+/- 1.5mm+/- 2mm+/- 1mm+/- 2mm
Warranty

QuadCore® Assured Panel Warranty

  • 25 years thermal performance

  • 25 years fire performance 

  • 25 years structural performance

  • 25 years environmental performance

  • Up to 30 years coating performance

Downloads

Access product brochures, datasheets, and technical documentation to support specification and project planning.

Viewing 2 downloads
kingspan-quadcore-ultratech-precision-panel-data-sheet-en-gb-ie.pdf

Quadcore Ultratech Precision Panel Data Sheet

Data Sheets
Download
kingspan-ultratech-precision-brochure-en-gb-ie.pdf

UltraTech Precision Brochure

Brochures
Download

Need Technical Support?

Send us your enquiry and our Tech-eXchange team will provide information and guidance to support your specification or project.

Products

Related Products

Explore related products and systems within our Precision range designed for a range of building applications in cleanroom envrionments.

AHC UltraTech Precision Panel Render
AHC UltraTech Precision Panel

A customisable, modular flush cleanroom system with an aluminium honeycomb core.

K-Roc UltraTech Precision Panel Render
K-Roc UltraTech Precision Panel

Insulated panel system featuring a mineral fibre core.

UltraTech Precision Door
UltraTech Precision Door

Flush door system suitable for stringently controlled hygienic environments.

Ultratech Precision Vision Panel Render
UltraTech Precision Vision Panel

Fully flush glazed units, suitable for environments requiring flush fittings.

UltraTech Precision Ceiling Suspension System Render
UltraTech Precision Ceiling Suspension

A flush ceiling surface from within a cleanroom environment.

Case Studies

Related Projects

See how QuadCore UltraTech Precision Panels are used in real projects across a variety of sectors.

St. Vincent's University Hospital

St. Vincent's University Hospital

One of the world’s leading academic teaching hospitals, through an expansion of services, established the need for a state-of-the-art aseptic compounding unit (ACU).

Convatec

Convatec

Convatec required a cleanroom to house multiple bonding machines and to assist with manufacturing.

St James's Hospital

St James's Hospital

An innovative new Aseptic Compounding Unit at St. James’s Hospital, Dublin.

How can we help?

Get in touch today to discuss your needs and discover how we can support you.