Clifton Comprehensive School
At the time of the fire, the construction of Clifton Comprehensive School in Rotherham, UK had just been completed but the building was not yet in use. The roof of the building was constructed of our insurer-approved PIR core insulated panels.
Real fire case study
Location: Rotherham, UK
Business activity: School
Panel delivery date: December 2003
Date of fire: July 2004

Clifton Comprehensive School
The fire started in an enclosed passageway linking two open air plant areas on the roof. There was scaffolding at the rear of the premises which gave access to the roof and the fire was thought to have been caused by accidental or malicious ignition of roof sealant.
The plastic and glass components of the fire alarm and light fittings had shattered / melted and, although delamination of the inner skin occurred, the core and outer skin of the insulated panels remained undistorted. The deformation of the purlins immediately above the seat of the fire gives indication of its severity.
Protection against fire spread
The classrooms were separated from the passageway by compartment walls. The fire did not spread to the classrooms and firefighters observed only light smoke in some of these rooms. There was no indication of any heat or smoke migration through the insulation of the roofing sheets and the fire service commented that the roof panels did not contribute to fire spread.
Had the roof been of a more traditional construction (e.g. tiles on timber battens with a felt membrane), the fire may have been severe enough to ignite the roof construction and cause the fire to spread over the compartment walls.
Our insurer-approved PIR core insulated roof panels:
Did not contribute to the cause of the fire
Did not contribute to fire spread to any other area of the building
Assisted in containing the fire
Click here to download the full report for Clifton Comprehensive School which was conducted by Tenos, this independent report gives a comprehensive overview of the fire and the performance of the insurer-approved Kingspan insulated panels.

Discover More
Wharfedale Hospital
Insurer-approved PIR core insulated panels cladding this hospital building prevented fire spread
Food Preparation Facility
Despite an extreme fire the insurer-approved PIR core insulated panels prevented fire spread
Retail Distribution Centre
Despite direct impingement from an extensive fire load, damage was localised
Spider Transport
Insurer-approved PIR core insulated panels prevented fire spread despite direct exposure to flame
How can we help?
Get in touch today to discuss your needs and discover how we can support you.