Skip to main content

Kingspan Insulated Panels

Welcome to Kingspan Insulated Panels

Technical Information

Detailed technical information for QuadCore Coldstore Panel, covering dimensions, thermal and acoustic performance, fire classification and warranty information. Full product information is available in the product data sheet.

Fire Performance Matrix

View our Fire Performance Matrix for wall and ceiling applications of QuadCore Coldstore Panel.

Available Lengths

Standard lengths: 1.8 - 14.5 m

Longer lengths (non-standard): 14.5 - 21.0 m

Shorter lengths (non-standard): Below 1.8m

Note: Additional costs and transport restrictions may apply for non-standard lengths. All lengths may change for export (outside of the UK and Ireland).

Dimensions, Weight & Thermal Performance
Dimensions, Weight & Thermal Performance
Core thickness (mm)506080100125150175200220
U-value (W/m².K)0.380.310.230.180.150.120.100.090.08
Weight (kg/m²)10.110.511.212.012.913.914.815.816.5

Notes: These values are in accordance with BS EN 14509, calculated using Finite Element Analysis, and take into account any thermal bridging through the longitudinal joint. The U-values have been calculated using an aged thermal conductivity value of 0.018 W/m.K.

Certification and Testing

Reaction to Fire

QuadCore Coldstore Panels are classified B-s1,d0, when tested on the internal face of the product, according to the European Reaction to Fire classification system (Euroclasses) BS EN 13501–1: 2018 under the certified name KS1100CS when using the following internal liners: CLEANsafe 15, CLEANsafe 25, CLEANsafe 55, CLEANsafe120, AQUAsafe 55. Please contact Kingspan Tech-eXchange for information relating to the external face.

Roof Applications

QuadCore Coldstore Panels are tested to:

Broof(t4) to BS EN 13501-5: 2016 under the certified name KS1100CS QuadCore for panel thicknesses 50 – 220mm and roof pitch 0 - 10°.

Please contact Kingspan Tech-eXchange for information relating to the specific arrangement required for Broof(t4) classification.

Fire Resistance

Fire resistance classifications are subject to panel thickness, orientation, method of assembly, and steel coating. Please contact Kingspan Tech-eXchange for project specific details.

Insurer Approvals

QuadCore Coldstore Panels are tested to:

LPS 1181 Part 1: Issue 1.2 Requirements and tests for built-up cladding and sandwich panel systems for use as the external envelope of buildings certified to:

-LPS 1181-1 Grade EXT-B under the certified name Kingspan IPN QuadCore KS600-1200 AB (roof/ceiling panel) for thicknesses 50 - 200 mm

LPS 1181 Part 2: Issue 2 Requirements and tests for sandwich panels and built-up systems for use as internal constructions in buildings certified to:

-LPS 1181-2 Grade INT-3 under the certified name Kingspan IPN QuadCore KS600-1200 CS (wall and ceiling panels) for thicknesses 80 - 200 mm

-LPS 1181-2 Grade INT-2 under the certified name Kingspan IPN QuadCore KS600-1200 CS (wall panel) for thicknesses 100 - 200 mm

-LPS 1181-2 Grade INT-2 under the certified name Kingspan IPN QuadCore KS600-1200 CS (ceiling panel) for thicknesses 125 - 200 mm

LPS 1208: Issue 2.2 LPCB test and performance requirements for walls, cavity barriers, floors and roofs certified to:

-FR30 under the certified name Kingspan IPN QuadCore KS600-1200 CS (wall panel) for thicknesses 100 - 220 mm

-FR30 under the certified name Kingspan IPN QuadCore KS600-1200 CS (ceiling panel) for thicknesses 100 - 220 mm

-FR60 under the certified name Kingspan IPN QuadCore KS600-1200 CS (wall panel) for thicknesses 175 - 220 mm

-FR60 under the certified name Kingspan IPN QuadCore KS600-1200 CS (ceiling panel) for thicknesses 175 - 220 mm

Please contact Kingspan Tech-eXchange for information relating to the specific arrangement required for LPS 1208 classification.

FM 4880 approval standard for class 1 fire rating of building panels or interior finish materials under the certified name KS1100CS and KS1200CS for thicknesses 50 – 220mm

FM 4881 approval standard for class 1 exterior wall systems under the certified name KS1100CS and KS1200CS for thicknesses 50 – 220mm

FM 4882 approval standard for class 1 interior wall and ceiling materials or systems for smoke sensitive occupancies under the certified name KS1100CS and KS1200CS for thicknesses 50 – 220mm

Insurer approvals are large scale testing regimes that provide objective third-party testing, which is underpinned by quarterly, bi-annual and annual factory surveillance audits (depending on the region) to verify compliance. Insurer approvals are subject to panel thickness, cover width, orientation, method of assembly, steel coating and manufacturing facility. Please contact Kingspan Tech-eXchange for further information.

LPCB / FM Approval Marks
Certification and Testing LEC

Reaction to Fire

QuadCore Coldstore LEC Panels are classified B-s1,d0, when tested on the internal face of the product, according to the European Reaction to Fire classification system (Euroclasses) BS EN 13501-1:2018 under the certified name KS1100 CS when using the following internal liners: CLEANsafe 15, CLEANsafe 25 and CLEANsafe 120.

Please contact Kingspan Tech-eXchange for information relating to the external face.

Roof Applications

QuadCore Coldstore LEC Panels are tested to: Broof(t4) to BS EN 13501-5: 20™ under the certified name KS1100 CS QuadCore for panel thicknesses 50 – 220mm and roof pitch 0 – 10°.

Please contact Kingspan Tech-eXchange for information relating to the specific arrangement required for Broof(t4) classification.

Fire Resistance

Fire resistance classifications are subject to panel thickness, orientation, method of assembly, and steel coating. Please contact Kingspan Tech-eXchange for project specific details.

Insurer Approvals

QuadCore Coldstore LEC Panels are tested to:

LPS 1181 Part 1: Issue 1.2 Requirements and tests for built-up cladding and sandwich panel systems for use as the external envelope of buildings certified to: LPS 1181-1 Grade EXT-B under the certified name Kingspan IPN QuadCore KS600-1200 AB (roof/ceiling panel) for thicknesses 50 – 200mm.

LPS 1181 Part 2: Issue 2 Requirements and tests for sandwich panels and built-up systems for use as internal constructions in buildings certified to: – LPS 1181-2 Grade INT-3 under the certified name Kingspan IPN QuadCore KS600-1200 CS (wall and ceiling panels) for thicknesses 80 – 200mm

LPS 1181-2 Grade INT-2 under the certified name Kingspan IPN QuadCore KS600-1200 CS (wall panel) for thicknesses 100 – 200mm

LPS 1181-2 Grade INT-2 under the certified name Kingspan IPN QuadCore KS600-1200 CS (ceiling panel) for thicknesses 125 – 200mm.

LPS 1208: Issue 2.2 LPCB test and performance requirements for walls, cavity barriers, floors and roofs certified to:

– FR30 under the certified name Kingspan IPN QuadCore KS600-1200 CS (wall panel) for thicknesses 100 – 220mm.

– FR30 under the certified name Kingspan IPN QuadCore KS600-1200 CS (ceiling panel) for thicknesses 100 – 220mm

– FR60 under the certified name Kingspan IPN QuadCore KS600-1200 CS (wall panel) for thicknesses 175 – 220mm

– FR60 under the certified name Kingspan IPN QuadCore KS600-1200 CS (ceiling panel) for thicknesses 175 – 220mm

Please contact Kingspan Tech-eXchange for information relating to the specific arrangement required for LPS 1208 classification.

FM 4880 approval standard for class 1 fire rating of building panels or interior finish materials under the certified name KS1100 CS and KS1200 CS for thicknesses 50 – 220mm.

FM 4881 approval standard for class 1 exterior wall systems under the certified name KS1100 CS and KS1200 CS for thicknesses 50 – 220mm.

FM 4882 approval standard for class 1 interior wall and ceiling materials or systems for smoke sensitive occupancies under the certified name KS1100 CS and KS1200 CS for thicknesses 50 – 220mm.

Insurer approvals are large scale testing regimes that provide objective third-party testing, which is underpinned by quarterly, bi-annual and annual factory surveillance audits (depending on the region) to verify compliance. Insurer approvals are subject to panel thickness, cover width, orientation, method of assembly, steel coating and manufacturing facility. Please contact Kingspan Tech-eXchange for further information.

LPCB / FM Approval Marks
Acoustic
Sound Reduction Index (SRI)
Hz*631252505001k2k4k8k
SRI1516212417444651

Sound Reduction Index (SRI)

* Frequency

QuadCore Coldstore Panels have a single figure weighted sound reduction Rw(C;Ctr) = 26 (-4;-7) dB, rating according to BS EN ISO 717-1:2013. Results are based on QuadCore Coldstore 80mm thick panel, measurement of Sound Reduction Index to BS EN ISO 10140-2: 2010.

Heat Transmission
Heat Transmission
Panel thickness (mm)506080100125150175200220
U-value (W/m2K)0.380.310.230.180.150.120.100.090.08
Temperature difference (°C)
103.603.002.251.801.441.201.030.900.82
155.404.503.382.702.161.801.541.351.23
207.206.004.503.602.882.402.061.801.64
259.007.505.634.503.603.002.572.252.05
3010.809.006.755.404.323.603.092.702.45
3512.6010.507.886.305.044.203.603.152.86
4014.4012.009.007.205.764.804.113.603.27
4516.2013.5010.138.106.485.404.634.053.68
5018.0015.0011.259.007.206.005.144.504.09
5519.8016.5012.389.907.926.605.664.954.50
6021.6018.0013.5010.08.647.206.175.404.91
6523.4019.5014.6311.709.367.806.695.855.32
7025.2021.0015.7512.6010.088.407.206.305.73
7527.0022.5016.8813.5010.809.007.716.756.14
8028.8024.0018.0014.4011.529.608.237.206.55

Thermal Conductivity (λ) 0.018 W/m.K

Notes: The heat gain by conduction should be limited to 10W/m2, for enhanced energy performance, the heat gain by conduction should be limited to 8W/m2 (Guidelines for the Design, Specification, Construction, Maintenance and Fire Management of Insulated Envelopes for Temperature Controlled Environments).

Product Tolerance

Cut to Length (≤3m): ±5mm

Cut to Length (>3m): ±10mm

Cover Width: ±2mm

Thickness (Core ≤ 100mm): ±2mm

Thickness (Core > 100mm): ±2%

Flatness (per meter): ±1.5mm

End Square: ±3mm

Warranty

QuadCore Assured Panel Warranty


25 years thermal performance
25 years fire performance
25 years structural performance
25 years environmental performance
Up to 40 years coating performance

NBS Specification
Environmental Product Declaration (EPD)

Downloads

Access product brochures, datasheets, and technical documentation to support specification and project planning.

Viewing 1-6 of 21 downloads
kingspan-quadcore-coldstore-panel-data-sheet-en-gb-ie.pdf

QuadCore Coldstore Panel Data Sheet

Data Sheets
Download
kingspan-quadcore-lec-coldstore-panel-data-sheet-en-gb-ie.pdf

QuadCore Coldstore LEC Panel Data Sheet

Data Sheets
Download
kingspan-quadcore-coldstore-dop-en-gb-ie.pdf

Declaration of Performance

Declaration of Performance (DoP)
Download
kingspan-quadcore-coldstore-fire-performance-matrix-table-gb-ie

Fire Performance Matrix

Test Reports / Classification
Download
kingspan-coldstore-panel-cutting-guidance-gb-ie

Panel Cutting Guidance

Download
kingspan-lps-1181-part-2-issue-2-3-certification-en-gb.pdf

LPS 1181 Part 2: Issue 2.3 Certificate of Product Approval

Test Reports / Classification
Download
Viewing 1-6 of 21 downloads

Need Technical Support?

Send us your enquiry and our Tech-eXchange team will provide information and guidance to support your specification or project.

Tools & Services

Technical Tools & Services

Access a range of tools to support design, specification, and project delivery

Multiple monitors showing calculations
Calculations

Project-specific fastener requirements, U-value calculations, and condensation risk analysis.

Fire
Fire Resistance

Fire performance data and guidance for insulated wall panel systems.

Laptop showing product selector
Product Selector

Identify suitable panel options based on project requirements and performance criteria.

Products

Complementary Products

Explore complementary systems and solutions designed for a range of building envelope applications.

Wall panels on industrial building
Wall Solutions

Our insulated wall panels are designed for industrial, commercial and a range of other applications. Our wall panels not only provide high thermal and environmental performance, but also offer a striking exterior finish.

Roof panels on industrial building
Roof Solutions

Insulated roof panels designed for use in commercial and industrial roof systems. Suitable for new build and refurbishment projects where thermal performance and ease of installation are key considerations.

PowerPanel close up on industrial roof
Solar Solutions

Discover our range of solar solutions, designed to align with insulated panel roof constructions. Suitable for a range of building types, these solutions support the integration of on-site renewable energy into the overall building design.

Dri-Design Cassette
Rainscreen Facades

Discover our Rainscreen Solutions Designed for durability, efficiency, and design flexibility

Case Studies

Related Projects

See how QuadCore Coldstore Panels are used in real projects across commercial and industrial sectors

Alpha Solway distribution centre

Alpha Solway

A distribution centre in Warrington has been converted into a high-quality manufacturing facility for producing personal protective equipment for the NHS.

Jones Food Company Vertical Farm

Jones Food Company

QuadCore Coldstore contributes to one of the world's largest, most advanced vertical farms, boasting 15,000 square metres.

Salford Energy Test Centre

Energy House 2.0 Salford University

Designed to achieve high precision-temperature control, Energy House 2.0 is Salford University's unique energy performance test centre.

Fyffes Distribution Centre

Fyffes

One of the world’s oldest and largest tropical produce importer facilitates further sustainable expansion in Ireland with the help of a range of our panels.

How can we help?

Get in touch today to discuss your needs and discover how we can support you.