Technical Information
Detailed technical data for QuadCore® UltraTech Versatile Panels, including thermal performance, fire classification, acoustics and more.
Applications
QuadCore® UltraTech Versatile Panels are designed for all internal cleanroom applications including new build and refurbishment projects.
Available Lengths
| Standard Lengths (m) | 1.8 - 14.5 |
| Longer Lengths (non-standard) (m) | 14.5 - 21.0 |
| Shorter Lengths (non-standard) (m) | Below 1.8 |
Note: Additional costs and transport restrictions may apply for non-standard lengths. All lengths may change for export (outside of the UK & Ireland).
Dimensions, Weight & Thermal Performance
| Core Thickness (mm) | 50 | 60 | 80 | 100 | 125 | 150 | 175 | 200 | 220 |
| U-Value (W/m²K) | 0.38 | 0.31 | 0.23 | 0.18 | 0.15 | 0.12 | 0.10 | 0.09 | 0.08 |
| R-Value (m²K/W) | 2.63 | 3.23 | 4.35 | 5.560 | 6.67 | 8.33 | 10.00 | 11.11 | 12.50 |
| Weight (kg/m²) | 10.1 | 10.5 | 11.2 | 12.0 | 12.9 | 13.9 | 14.8 | 15.8 | 16.5 |
These values are in accordance with BS EN 14509, using Finite Element Analysis, and take into account any thermal bridging through the longitudinal joint.
The U-Values have been calculated using an aged thermal conductivity value of 0.018W/mK.
Air Tightness
QuadCore® UltraTech Versatile Panel joints achieve an air tightness of 0.02m³/h.m at 50Pa in accordance with BS EN 14509 with joint sealed using gun grade sealant.
For further information on air tightness please contact Kingspan Tech-eXchange.
Certification and Testing
Reaction to Fire
QuadCore® UltraTech Versatile Panels are classified B-s1,d0, when tested on the internal face of the product, according to the European Reaction to Fire classification system (Euroclasses) BS EN 13501–1: 2007+A1: 2009 under the certified name KS1100UT-S/KS1200UT-S and BS EN 13501-1:2018 under the certified name KS1100UT-S/KS1200UT-S when using the following internal liners:
CLEANsafe 15, CLEANsafe 25, CLEANsafe 55, and CLEANsafe 120.
Please contact Kingspan Tech-eXchange for information relating to the external face.
Fire Resistance
Fire resistance classifications are subject to panel thickness, orientation, method of assembly, and steel coating.
Please contact Kingspan Tech-eXchange for project specific details.
Insurer Approvals
LPS 1181 Part 2: Issue 2 Requirements and tests for sandwich panels and built-up systems for use as internal constructions in buildings certified to:
LPS 1181-2 Grade INT-3 under the certified name Kingspan IPN QuadCore KS600-1200 CS (wall and ceiling panels) for thicknesses 80 - 200 mm
LPS 1181-2 Grade INT-2 under the certified name Kingspan IPN QuadCore KS600-1200 CS (wall panel) for thicknesses 100 - 200 mm
LPS 1181-2 Grade INT-2 under the certified name Kingspan IPN QuadCore KS600-1200 CS (ceiling panel) for thicknesses 125 - 200 mm.
LPS 1208: Issue 2.2 LPCB test and performance requirements for walls, cavity barriers, floors and roofs certified to:
FR30 under the certified name Kingspan IPN QuadCore KS600-1200 CS (wall panel) for thicknesses 100 - 220 mm
FR30 under the certified name Kingspan IPN QuadCore KS600-1200 CS (ceiling panel) for thicknesses 100 - 220 mm
FR60 under the certified name Kingspan IPN QuadCore KS600-1200 CS (wall panel) for thicknesses 175 - 220 mm
FR60 under the certified name Kingspan IPN QuadCore KS600 - 1200 CS (ceiling panel) for thicknesses 175 - 220 mm
Please contact Kingspan Tech-eXchange for information relating to the specific arrangement required for LPS 1208 classification.
FM 4880 approval standard for class 1 fire rating of building panels or interior finish materials under the certified name KS1100UT-S and KS1200UT-S for thicknesses 50 – 220mm.
FM 4881 approval standard for class 1 exterior wall systems under the certified name KS1100UT-S and KS1200UT-S for thicknesses 50 – 220mm.
FM 4882 approval standard for class 1 interior wall and ceiling materials or systems for smoke sensitive occupancies under the certified name KS1100UT-S and KS1200UT-S for thicknesses 50 – 220mm.
Insurer approvals are large scale testing regimes that provide objective third-party testing, which is underpinned by quarterly, bi-annual and annual factory surveillance audits (depending on the region) to verify compliance. Insurer approvals are subject to panel thickness, cover width, orientation, method of assembly, steel coating and manufacturing facility.
Please contact Kingspan Tech-eXchange for further information.

Acoustic
| Frequency (Hz) | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 |
| SRI (dB) | 20 | 15 | 17 | 23 | 18 | 25 | 40 | 46 |
QuadCore® UltraTech Versatile Panels have a predicted single figure weighted sound reduction of Rw = 24dB. Results are based on panels of similar profile and core material.
Product Tolerances
| Cut to Length (> 3m) | Cover Width | Thickness (Core <100mm) | Thickness (Core >100mm) | Flatness (per m) | End Square |
| +/- 10mm | +/- 2mm | +/- 2mm | +/- 2% | +/- 1.5mm | +/- 3mm |
Warranty
QuadCore Assured Panel Warranty
25 years thermal performance
25 years fire performance
25 years structural performance
25 years environmental performance
Up to 40 years coating performance
Downloads
Access product brochures, datasheets, and technical documentation to support specification and project planning.