Technical Information
Applications
JI Vulcasteel Roof Roof Panels are through-fix, trapezoidal profiled, insulated roof panels which can be used for building applications with roof pitches of 5° or more after deflection.
Dimensions, Thermal Performance & Weight
| Total R-Value (m²K/W) | Total R-Value (m²K/W) | ||||
|---|---|---|---|---|---|
| Panel Nominal Thickness (mm) | Overall Thickness (mm) | Product R-Value at 23°C (m²K/W) | Heat Flow Out (Winter) | Heat Flow In (Summer) | Weight* (kg/m2) |
| 80 | 117 | 1.80 | 2.06 | 1.90 | 18.6 |
| 100 | 137 | 2.22 | 2.52 | 2.30 | 20.6 |
| 120 | 157 | 2.65 | 2.97 | 2.71 | 22.6 |
| 150 | 187 | 3.29 | 3.65 | 3.31 | 25.6 |
| 175 | 212 | 3.82 | 4.21 | 3.81 | 28.0 |
| 200 | 237 | 4.35 | 4.77 | 4.31 | 30.7 |
Declared Product R-Value is calculated in accordance with AS/NZS 4859.1: 2018 as required for compliance to the National Construction Code.
The R-Values shown above are the total R-Values for the building element as required by the Energy Provisions of the National Construction Code, calculated in accordance with AS/NZS 4859.2: 2018. JI Vulcasteel Roof Panels are manufactured, tested and packaged in conformance with AS/NZS 4859.1: 2018.
* Actual weight subject to vary ±10% due to manufacturing and raw material tolerances.
Insulation Core
JI Vulcasteel Roof Panels are manufactured with a 100kg/m³ non-combustible stone wool core with a tolerance of +10/-5 kg/m³.
Certification and Testing
Reaction to Fire:
JI Vulcasteel Roof Panel is a bonded laminated material. It achieves the following fire test results, as required by clause C2D10 (6)(g) of the National Construction Code (NCC). Therefore, it can be used wherever a non-combustible material is required by the NCC.
JI Vulcasteel stonewool core is not-deemed combustible when tested to AS 1530.1 1994 (2016)
JI Vulcasteel Panel skin (uncoated) is not-deemed combustible when tested to AS 1530.1 1994 (2016)
Ignitability Index: 0 as per AS/NZS: 1530.3: 1999
Spread of Flame Index: 0 as per AS/NZS: 1530.3: 1999
Heat Evolved Index: 0 as per AS/NZS: 1530.3: 1999
Smoke Developed Index: 2 as per AS/NZS: 1530.3: 1999
There are two factory-applied adhesive layers applied during the manufacture of the product. Each adhesive layer does not exceed 1 mm in thickness and the total thickness of the adhesive layers does not exceed 2 mm in thickness.
Insurer Approvals:
JI Vulcasteel Roof Panels are tested to FM 4471 approval standard for class 1 roof panels under the certified name JI Vulcasteel Roof for thicknesses 80mm to 200mm.
Insurer approvals are large scale testing regimes that provide objective third-party testing, which is underpinned by quarterly, half-yearly and yearly factory surveillance audits (depending on the region) to verify compliance. Insurer approvals are subject to panel thickness, width, orientation, method of assembly, steel coating and manufacturing facility.
Please contact our Technical Team for project specific details.
Acoustic Performance
For specific acoutic information please contact Technical Team.
| Core Thickness | 80 | 100 | 120 | 150 | 175 | 200 |
|---|---|---|---|---|---|---|
| SRI (dB) | 30 | 30 | 31 | 31 | 33 | 31 |
Product Tolerance
| Length | ±10 mm |
|---|---|
| Cover Width | ±2 mm |
| Thickness | ±2 mm |
| Facing Squareness | ±2 mm |
| Corners (leg length) | ±3 mm |
| Flatness | 1.5 mm from the theoretical flat plane over a distance of 700 mm |
| Joint Gap | ±2 mm |
Available Lengths
2.5 m - 11.8 m.
Materials and Coating
External Weather Sheet/Internal Liner:
Metallic coated steel in accordance with EN10326
External Weather Sheet Colour: As per Kingspan Ultra standard range
Internal Liner Sheet colour: PE25 (RAL 9010)
Seals
All panel joints have factory applied seal fitting on the internal liner joint of the side-lap to automatically seal the adjacent panels.
Panel End Cut Back
Min Cut Back: 50mm
End Lap: 150mm
Eaves Cut Back: 80mm
Max Cut Back*: 300mm
Note*:Cut backs only possible in increments of 10mm. For cut backs larger than 150mm, the core material and the steel at the cut back will not be removed and will have to be carried out on site by the installer.
Downloads
View JI Vulcasteel Roof Panel Technical Documents